Inert Gas Fire Suppression Systems | HD Fire Protect https://www.hdfire.com/products-solutions/inert-gas-fire-suppression-systems/ Wed, 12 Feb 2025 06:05:12 +0000 en-US hourly 1 https://wordpress.org/?v=6.8.3 https://www.hdfire.com/wp-content/uploads/2025/04/cropped-hdfirelogo-32x32.png Inert Gas Fire Suppression Systems | HD Fire Protect https://www.hdfire.com/products-solutions/inert-gas-fire-suppression-systems/ 32 32 HD-INERTSYS® Inert Gas Suppression System https://www.hdfire.com/products-solutions/inert-gas-fire-suppression-systems/hd-inertsys-inert-gas-suppression-system/ Mon, 08 Jul 2024 09:57:44 +0000 https://www.hdfire.com/?post_type=product&p=20493 Designed for IG55 (50% Argon and 50% Nitrogen), IG541 (52% Nitrogen, 40% Argon and 8% Carbon dioxide), IG100 (Nitrogen) and IG01 (Argon) agents Inert Gases are colourless, odourless, and electrically non conductive with a density approximately the same as air. Cylinder Sizes: 80 and 140 litre Operating Pressure: 200 bar (2900 psi), 300 bar (4351

The post HD-INERTSYS® Inert Gas Suppression System appeared first on hdfire.

]]>
  • Designed for IG55 (50% Argon and 50% Nitrogen), IG541 (52% Nitrogen, 40% Argon and 8% Carbon dioxide), IG100 (Nitrogen) and IG01 (Argon) agents
  • Inert Gases are colourless, odourless, and electrically non conductive with a density approximately the same as air.
  • Cylinder Sizes: 80 and 140 litre
  • Operating Pressure: 200 bar (2900 psi), 300 bar (4351 psi), depending on volume and concentration requirements
  • Releasing Device: Manual, Pneumatic, Electro-Magnetic
  • Available with Selector/Directional valves for protection of multiple areas with a common gas bank
  • Approval: VdS
  • System Design Calculations performed using VdS calculation software